AOIP-monofunction panel meter for electrical measurements (Model:VNE2)

6
436
Vui lòng liên hệ với chúng tôi– chúng tôi sẽ liên hệ lại với khách hàng bằng điện thoại hoặc email.
Lưu ý: Tham khảo ý kiến của nhân viên INO sẽ giúp bạn tiết kiệm được thời gian và chi phí khi cần mua sắm. ​​Với sự tư vấn của chúng tôi, bạn sẽ không gặp khó khăn khi tìm hiểu về đặc tính của sản phẩm cần mua.

VNE2 is a monofunction 2,000 point digital panel meter 72 x 24 mm for electrical measurements in voltage, current and process signals. They are particularly adapted to measurements in industrial areas: robust housing, connection through a removable screwing connector, high immunity to external noises, several types of power supply. AC current measurement can be performed using an external transformer insuring a good insulation to the instrument in regards to line potentials.

  • Panel meter size: 72 mm x 24 mm
  • IP40 protected
  • Measurement and display of:
    • DC and AC voltage up to 650 V
    • DC current up to 1,000 A with an external shunt
    • AC current up to 200 A
    • Process
  • 9 different power supplies available

Electrical measurement indicator

Type Range Resolution Accuracy (1 year)
(23°C ± 1°C)
Input impedance Comment
DC voltage 200 mV
2 V
20 V
200 V
650 V
100 μV
1 mV
10 mV
100 mV
1 V
0.1% + 100 μV
0.1% + 1 mV
0.1% + 10 mV
0.1% + 0.1 V
0.1% + 1 V
> 100 MΩ
1.1 MΩ
1 MΩ
1 MΩ
10 MΩ
Optional decimal point command
DC current On request
2 A
100 mV / 1000 pts
1 mA
0.2% + 1 mA Shunt 100 mV
0.1 Ω
External Shunt 10 – 100 – 1 000 A
or internal 2 – 20 – 200 mA
AC voltage 650 V 1 V 2 V 900 kΩ Band-width
40 Hz to 400 Hz
AC current 2 A
20 A
200 A

On request

1 mA
10 mA
100 mA
100 mV / 1000 pts
1% + 2 mA
1% + 20 mA
1% + 0.2 A
0.3% + 2
900 kΩ Delivered with transformer (2 – 20 ou 200 A) >For secondary of CT 1 or 5A non-included
Process signals with scaling 0 – 5 V
0 – 10 V
4 – 20 mA
0 – 20 mA
Display ± 2000
points
For scale begin and end
0.1 % of
scale end + 1
1 MΩ
1 MΩ
50 Ω
50 Ω
2 models, input and scale defined with order,
can be modified by user (D51 model is set in
factory: 4-20 mA/0-100 %). an analog output is
available as option.

Temperature coefficient: ≤ accuracy/10°C
Common rejection mode: ³ 110 dB at 50 Hz
Serial rejection mode: ³ 60 dB at 50 Hz

Further features

Linear analogue output 1 mV / digit
Acceptable load: ³  2kW 
Non insulated analogue output
External decimal dot commutation Command for V- models
Current transformer Suitable transformer is supplied with I 33, I 34 and I 35 models.
Primary 2 A, 20 A or 200 A.
Secondary 1 A.
200 mV on 0.2 Ω shunt.
Accuracy class 0.5 for 1 VA power
Frequency 50 / 60 Hz.
Primary connection by plugs for 2 A and 20 A ranges and metal
cable gland (∅<12mm) for 200 A range.
Zeroing and polarity Automatic
Sampling rate 2.5 samples / s

Resource & Download

Lưu ý: Nếu một thiết bị nào đó không được liệt kê ở đây, điều đó không có nghĩa rằng chúng tôi không hỗ trợ được bạn về thiết bị đó. Hãy liên hệ với chúng tôi để biết danh sách đầy đủ về thiết bị mà chúng tôi có thể hỗ trợ và cung cấp.
INO: Bán, Báo giá, tư vấn mua sắm và cung cấp, tư vấn sản phẩm thay thế; tương đương, hướng dẫn sử dụng, giá…VNĐ, …USD info@ino.com.vn | 02873000184 | AOIP-monofunction panel meter for electrical measurements (Model:VNE2).

Comments are closed.