Lưu ý: Tham khảo ý kiến của nhân viên INO sẽ giúp bạn tiết kiệm được thời gian và chi phí khi cần mua sắm. Với sự tư vấn của chúng tôi, bạn sẽ không gặp khó khăn khi tìm hiểu về đặc tính của sản phẩm cần mua.
Captures events like dips and swells, interruptions and rapid voltage changes, based upon ½ cycle rms values
Unique AutoTrend gives you fast insight into changes over time
With a single push of a button, the unique System Monitor gives you an overview of power system performance. It also checks that incoming power complies to EN50160 limits or to your own custom specifications
Logger: detailed, user-configurable long-term recording gives you the MIN, MAX and AVG readings of up to 100 parameters on all four phases. Averaging time can be selected down to 0.5 seconds (or 1 minute for 1 day’s recording, 10 minutes for 1 week, 30 minutes for 1 month or more
Two groups of four channels: simultaneously measure voltage and current on all three phases and neutral
Auto Scaling: easier trend analysis with automatic scaling of the vertical axis – so you will always view the waveforms on a full display
Meets the stringent 600 V CAT IV, 1000 V CAT III safety standard required for measurements at service entrance
Extensive data analysis: cursors and zoom can be used ‘live’ while taking the measurements, or ‘offline’ on stored measurement data. The stored measurements can also be transferred to Power Log software
Analyze every parameter on display
Measure and record power (W), VA and VARs. The Fluke 434/PWR adds the ability to record energy consumption
Logging function allows you to customize measurement selections and provides analysis of user-selectable parameters to find intermittent problems or relate PQ issues to other phenomena/events.
The System-Monitor overview screen gives instant insight into whether the voltage, harmonics, frequency, and the number of dips and swells fall outside the set limits.
Phasor diagram shows voltage and current unbalance, and helps verify connections
The full color display allows the use of industry-standard color-coding (user selectable) to correlate measurements with actual wiring
Fluke Power Log Software
Designed to quickly view recorded data, the built-in Power Log software displays all recorded parameters on interactive trends. Generate a profes¬sional looking report with the ‘PRINT’ function or copy and paste images into a report document manually. Customize the report generator to easily create your own formats.
Print reports and view graphs with Fuke Power Log sofware
Technical Data
Inputs
Number:
4 voltage and current (3 phases + neutral)
Maximum voltage:
1000 Vrms (6 kV peak)
Maximum sampling speed:
200 kS/s on each channel simultaneously
Volt/Amps/Hertz
Vrms (AC + DC)
Measurement range:
1 … 1000 V
Accuracy:
0.1% of Vnom
Vpeak
Measurement range:
1 … 1400 V
Accuracy:
5% of Vnom
Crest factor, voltage
Measurement range:
1.0 … > 2.8
Accuracy:
±5%
Arms (AC + DC)
Measurement range:
0 … 20 kA
Accuracy:
±0.5% ± 5 counts
Apeak
Measurement range:
1.4x rms value
Accuracy:
5%
Crest factor, A
Measurement range:
1 … 10
Accuracy:
±5%
Hz 50 Hz nominal
Measurement range:
40 … 70 Hz
Accuracy:
±0.01 Hz
Dips and swells
Vrms (AC+DC) ²
Measurement range:
0.0% … 100% of Vnom
Accuracy:
±0.2% of nominal voltage
Arms (AC+DC) ²
Measurement range:
0 … 20 kA'
Accuracy:
±1% ± 5 counts
Harmonics
Harmonic (interharmonic) (n)
Measurement range:
DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7
Lưu ý: Nếu một thiết bị nào đó không được liệt kê ở đây, điều đó không có nghĩa rằng chúng tôi không hỗ trợ được bạn về thiết bị đó. Hãy liên hệ với chúng tôi để biết danh sách đầy đủ về thiết bị mà chúng tôi có thể hỗ trợ và cung cấp.
INO: Bán, Báo giá, tư vấn mua sắm và cung cấp, tư vấn sản phẩm thay thế; tương đương, hướng dẫn sử dụng, giá…VNĐ, …USD info@ino.com.vn | 02873000184 | Fluke – Three Phase Power Analyzer (Model: 434).
Comments are closed.